560kVA 40kv AC Resonance Test System Applied on 100MW Generator 10kv 35kv Cable
Product Details
| Customization: | Available |
|---|---|
| After-sales Service: | Onsite and Remote Guidance |
| Warranty: | 2 Years Free Warranty Longlife Service |
Secured Trading Service
Diamond Member Since 2019
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Certification
Importers and Exporters
High Repeat Buyers Choice
Fast Delivery
The supplier's products already have relevant certification qualifications, including:
CE
CE
The supplier has import and export rights
More than 50% of buyers repeatedly choose the supplier
The supplier can deliver the goods within 15 days
Sign In to see all verified strength labels (19)
Find Similar Products
Basic Info.
- Model NO.
- EPCZ-560kVA / 40kV
- Type
- Transformer
- Application
- AC Hipot
- Certification
- CE, ISO9001: 2000, ISO, SGS
- Condition
- New
- Hv Reactor
- Epdk- 70kVA/40kv (40kv/1.75A)
- Exciting Transformer
- Epcb- 50kVA/3kv/6kv
- Variable Frequency Power Supply
- Epcz-100kw/380V
- Capacitive Divider
- Epfr- 40kv/0.003UF (60kv)
- Rated Output Voltage
- 0~40kv
- Resonant Voltage Waveform
- Sine Wave, Waveform Distortion Rate <1.0%
- Maximum Tested Product Current
- 1.75A 14A
- Maximum Test Capacity
- 560kVA
- Output Frequency
- 30~300Hz
- Working Time
- Continuous Working Time Is 60min Under Full Power
- Quality Factor
- 30~90
- Input Working Power
- Three-Phase 380V 5%, 50Hz
- Ambient Temperature
- -15c ~+40 C
- Relative Humidity
- <90rh%, No Condensation
- Noise
- Less Than 50dB
- Transport Package
- Plywood Case with Foam and Waterproof Plastics
- Specification
- Customized
- Trademark
- EP Hipot
- Origin
- Wuhan, China
- HS Code
- 9030339000
- Production Capacity
- 500/Year
Product Description
AC Resonance Test System EPCZ-560kVA / 40kV (can be applied on 100MW Generator and 10kV 35kV Cable)
The system is consisted by below units
· Variable Frequency Power supply
· Exciting Transformer
· HV Reactor
· Capacitive Divider
· Accessories Carrycase (connection wires)
Working Environment
· Environmental temperature: -15ºC to 40ºC
· Related humidity: ≤ 90% RH
· Altitude: ≤ 5000m
Application and requirement
1. Meet the 15.6kV/1000MVA generator AC withstand voltage test, capacitance≤1.4uF, test frequency 45~65Hz, test voltage U≤34.8kV (2Un+3). Test time: 1 minute
2. Meet 10kV/300mm2 cable AC withstand voltage test, capacitance≤1.12uF, test frequency 30~300Hz, test voltage U≤22kV. Test time: 5 minutes
3. Meet 35kV/300mm2 cable AC withstand voltage test, capacitance≤0.398uF, test frequency 30~300Hz, test voltage U≤52kV. Test time: 60 minutes
4. Meet the AC withstand voltage test of 10kV transformer, switch, etc., capacitance ≤0.0006uF, test frequency 30~300Hz, test voltage U≤35kV. Test time: 1 minute
Specification
Rated output voltage | Rated output voltage: 0~40kV |
Resonant voltage waveform | sine wave, waveform distortion rate <1.0% |
Maximum tested product current | 1.75A 14A |
Maximum test capacity | 560kVA |
Output frequency | 30~300Hz |
Working time | Continuous working time is 60min under full power output |
Quality factor | 30~90 |
Input working power | Three-phase 380V±5%, 50Hz |
Ambient temperature | -15ºC~+40ºC |
Relative humidity | <90RH%, no condensation |
Altitude | <5000m |
Noise | ≤50dB |
System performance characteristics
1. Make full use of our company's advantages in electronic measurement technology and electromagnetic compatibility, completely independently develop, design and produce all components of this set of equipment including: variable frequency power supply, excitation transformer, cast high voltage reactor and high-precision capacitive voltage divider.
2. Equipped with manual/automatic mode, large screen display, test parameter setting, and automatic timing and operation prompt functions.
3. Possess multiple protection functions, such as: overvoltage, overcurrent protection, discharge protection, detuning protection, etc.
Device capacity determination
The capacity of the equipment is designed to be 560kVA/40kV divided into 8 reactors, and the single reactor is 40kV/1.75A/70H in combination to meet the test requirements of the above-mentioned tested product.
Conclusion determination:
1. 15.6kV/1000MW generator, electric capacity ≤1.4μF, test frequency 45-65Hz, test voltage 34.8kV.
Use 8 reactors in parallel, at this time the inductance is L=70/8=8.6H
Test frequency f=1/2π√LC=1/(2×3.14×√8.6×1.4×10-6)=45.2Hz.
Test current I=2πfCUTest =2π×45.2×1.4×10-6×34.8×103=13.77A
Test frequency f=1/2π√LC=1/(2×3.14×√8.6×1.4×10-6)=45.2Hz.
Test current I=2πfCUTest =2π×45.2×1.4×10-6×34.8×103=13.77A
When 8 reactors are used in parallel, the maximum current is 14A, so 14A>13.77A, this set of equipment can meet the requirements of the above tested product.
2. 15.6kV/10MW generator, electric capacity ≤0.1μF, test frequency 45-65Hz, test voltage 34.8kV.Use 1 reactor, at this time the inductance is L=70
Test frequency f=1/2π√LC=1/(2×3.14×√70×0.1×10-6)=60Hz.
Test current I=2πfCUTest =2π×60×0.1×10-6×34.8×103=1.15A
Test frequency f=1/2π√LC=1/(2×3.14×√70×0.1×10-6)=60Hz.
Test current I=2πfCUTest =2π×60×0.1×10-6×34.8×103=1.15A
The maximum current of 1 reactor is 1.75A, so 1.75A>1.15A, this set of equipment can meet the requirements of the above tested product.
Conclusion: The device capacity is set to 560kVA/40kV, divided into 8 reactors, and the single reactor is 40/1.75A/70H in combination to meet the test requirements of the tested product.
More details on AC Resonance Test System EPCZ-560kVA / 40kV please contact EP Hipot Electric.

Company Profile




Packing & Delivery

FAQ

Send your message to this supplier