Customization: | Available |
---|---|
Type: | Universal Testing Machine |
Accuracy Grade: | 0.5 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Full current measurement range: | 0~10mA RMS |
Accuracy: ± (reading × 5% + 5uA) | |
Resistive current fundamental measurement accuracy (wired without interphase interference): | ± (reading × 5% + 5uA) |
Current harmonic measurement accuracy: | ± (reading × 10% + 10uA) |
Current channel input resistance: | ≤ 2Ω |
Reference voltage input range: | 25V~250V |
RMS Accuracy: ± (reading × 5% + 0.5V) | |
Voltage harmonic measurement accuracy: | ± (reading × 10%) |
Reference voltage channel input resistance: | ≥ 1800kΩ |
Battery continuous working time: | 8 hours or more |
Battery charging time: | 2 hours or more |
AC charging: | AC 220V ±10%, 50Hz ±1% |
Tester weight: | 5kg (without cable box) |
Tester size: | 34cm × 22cm × 20cm |