Customization: | Available |
---|---|
Accuracy Grade: | 0.5 |
Display: | Digital |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input power: | AC: 220V 25A, 50Hz |
Output current: | AC: 1000A/5V or 500A/10V |
Display: | LCD digital display, to show primary and secondary current, ratio and phase (polarity) at the same time. |
Primary current range: | 0 ~ 1100A, resolution: 0.1A |
Secondary current range: | 0~6A, resolution: 0.001A |
Accuracy: | RMS ± 0.5% |
Dual protection: |
overload electronic protection and software protection |
Operating environment: | Temperature -10~40ºC Relative humidity < 80% |
Volume: | 430mm × 260mm × 260mm |
Weight: | 28kg |
Rated Current | Time (Seconds) | Rated Current | Time (Seconds) |
1100% | 10S | 60% | 600S |
100% | 60S | 50% | 1800S |
90% | 90S | 40% | 3600S |
80% | 120S | <30% | Continuous |
70% | 240S | ||
The above is the first output time of power on. When the output time reaches the above time, the instrument must be cooled for more than 10 minutes before continuing to output current. |