Customization: | Available |
---|---|
After-sales Service: | Remote Guidance |
Warranty: | 1or 2 Years Free Warranty Longlife Service |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Current channel number | Standard six phase |
Voltage channel number | Standard six phase |
AC current output range | 30A / phase or 180A (six phase parallel) |
DC current output range | 10A DC /phase |
AC voltage output range | 120V AC /phase |
DC voltage output range | 160V DC / phase |
The each phase output when six phase current output (RMS): | 0~30A output precision 0.1 grade |
The each phase output when three phase current output (RMS): | 0~60A |
The six phase parallel current output(RMS): | 0~180A |
The allowed working value when the phase current work long time (RMS): | 10A |
The maximum output power of phase current | 450VA |
The maximum output power when six phase parallel current output | 1000VA |
The allowed working time when six phase parallel current maximum output | 10s |
Frequency range(fundamental wave) | 0~1000Hz |
Harmonic order | 0~20 |
Current output | 0~±10A / phase output precision 0.2 grade |
The maximum load voltage output | 20V |
Phase voltage output RMS value: | 0~120V output precision 0.1 grade |
Line voltage output RMS value: | 0~240V |
The output power of phase voltage/ line voltage: | 80VA / 100VA |
Frequency range(fundamental wave): | 0~1000Hz |
Harmonic orders: | 0~20 |
The output amplitude of phase voltage: | 0~±160V output precision 0.2 grade |
The output amplitude of line voltage: | 0~±320V |
The output power of phase voltage/ line voltage: | 70VA / 140VA |
On-off input | 8 channels |
Idle contact | 1~20mA,24V |
Electric potential contacts | "0":0 ~ +6V; "1":+11 V ~ +250 V |
4 channels output | DC:220 V/0.2 A;AC:220 V/0.5 A |