Customization: | Available |
---|---|
Display: | LCD |
Type: | Transformer Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Accuracy: | Cx: | ±(read ×1%+1PF) | |
Tgδ: | ±(read ×1%+0.00040) | ||
Anti interference: | Frequency conversion anti interference, under 200% interference, still can reach above accuracy. | ||
Capacitance range: | Internal HV: | 3PF~50000PF/12kV 60PF~1μF/0.5kV | |
External HV: | 3PF~1.5μF/12kV 60PF~30μF/0.5kV | ||
Resolution: | Max. 0.001PF, 4 significant figures | ||
Tgδ range: | Unlimited, resolution: 0.001%, capacitance, inductance, resistance can be identified automatically. | ||
Test current range: | 10μA~5A | ||
Inner HV: | Setting voltage range: | 0.5~12kV | |
Max. Output current: | 200mA | ||
Increase/decrease voltage: | Continuous slide regulating | ||
Voltage precision: | 2% | ||
Voltage resolution: | 1V | ||
Test frequency: | 45, 50, 55, 60, 65Hz single frequency | ||
45/55Hz, 55/65Hz, 47.5/52.5Hz auto double frequency conversion | |||
Frequency precision: | ±0.01Hz | ||
Outside HV: | UST Positive connection max. Test current 5A, Power frequency or frequency conversion 40-70Hz | ||
GST Negative connection max. Test current: 12kV/5A, power frequency or frequency conversion 40-70Hz | |||
CVT self excitation LV output: | Output voltage 3~50V, output current 3~30A | ||
Measuring duty: | About 36s, it depend on measuring methods | ||
Input power supply: | 180V~270VAC, 50Hz/60Hz±1%, local supply or by generator. | ||
RS232 | |||
Build-in thermal printer | |||
Environmental Temperature: | -10ºC~50ºC | ||
Relative humidity: | <90% | ||
Oversize & weight: | 460×360×350mm 28kg |