| Power Supply: | AC 220V ± 10%, unlimited frequency | |
| Power Output: | Maximum output voltage AC300V | Voltage Precision 0.5% |
| Current Precision 0.5% | ||
| Max. output current: 8A | ||
| Output frequency: 45Hz, 55Hz | ||
| Measuring Range: | capacitance: 0.1 ~ 50μF | |
| Impedance: 0.1 ~ 400Ω | ||
| Impedance angle -180°~ +180° | ||
| Measurement Resolution | Capacitance: 0.0001μF | |
| Impedance: 0.0001Ω | ||
| Impedance angle: 0.0001 ° | ||
| Measurement Accuracy | Capacitance: | ≥1µF, ±1% reading ±0.01µF |
| <1µF, ±2% reading ±0.01µF | ||
| Resistance: | ≥1Ω ±1% reading ±0.01Ω | |
| <1Ω ±2% reading ±0.01Ω | ||
| Impedance angle: | ±0.2° (voltage>1.0V) | |
| ±0.3° (voltage:0.2V~1.0V) | ||
| Anti-Interference Parameter | Interference voltage: 10kV (30kV is at option) | |
| Interference current: 30A (60A is at option) | ||
| Dimension: | All-in-one: 530mm(L)*410(W)*510mm(H) | |
| Separated: 410(L)*330(W)*390(H) (each unit) | ||
| Weight: | 65kg (all-in-one type) | |
| Anti-Interference Principle | Frequency conversion method | |
| Working Environment | - 20 ºC ~ 50 ºC RH < 80% | |