Function |
Insulation resistance test, voltage test |
Base conditions |
23°C±5°C,below 75%rh |
Rated voltage(V) |
250, 500, 1000, 2500, 5000V, 10kV |
Test Voltage(V) |
rated voltage×(1±10%) |
Insulation Resistance Range(GΩ) |
0.01MΩ~1000GΩ |
Insulation Resistance Insulation |
0.01MΩ |
DC Voltage Range |
0~1000V |
DC Voltage resolution |
0.1V |
AC Voltage Range |
0~750V |
AC Voltage resolution |
0.1V |
Output short-circuit Current |
≥3mA(5kV) |
Absorption Ratio and Polarization Index Measurement |
Have |
Power Supply |
12V rechargeable battery |
Backlight |
Controllable gray screen backlight, suitable for use in dim places |
Display mode |
4-bit large LCD display, gray screen backlight |
LCD display size |
108mm×65mm |
Instrument size |
L/W/H:277.2mm×227.5mm×153mm |
USB interface |
With USB interface, software monitoring, storage data can be uploaded to the computer, save the print |
Communication Line |
USB communication line 1PC |
Test Line |
High voltage robs red 3meter, high voltage test line black 1.5meter, green 1.5meter |
Data Storage |
500 groups, "FULL" symbol indicates that storage is full |
Data Review |
Data review function: "MR" symbol display |
Overflow Display |
Exceed measurement range overflow function: "OL" symbol display |
Alarm Function |
Alarm when the measured value exceeds the alarm setting value |
Power Consumption |
Standby: 30mA Max (backlight off) |
Turn on backlight: 42mA Max |
Measure:300mA Max (backlight off) |
Instrument weight |
2720g (including battery) |
Battery voltage |
When the battery voltage is low, low battery symbol " " will display |
Automatic shut-down |
automatic shutdown after 15 minutes boot |
Insulation Resistance |
≥50MΩ (between Measuring line and housing) |
Pressure Resistance |
AC3kV/50Hz 1min |
Working Temperature and Humidity |
-10ºC~+50ºC<85%RH |
Storage Temperature and Humidity |
-15ºC~+55ºC<90%RH |
Suitable for Safety Regulations |
IEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529(IP54) pollution grade 2, CAT III 300V |