24V  48V  110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary Battery

Product Details
Customization: Available
Type: Battery Packs Testing
Test Region: Charge and Discharge
Manufacturer/Factory, Trading Company
Diamond Member Since 2019

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
1000000 RMB
Plant Area
>2000 square meters
  • 24V  48V  110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary Battery
  • 24V  48V  110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary Battery
Find Similar Products

Basic Info.

Model NO.
EPFD Series
Application
Battery Discharge Testing
Customized
Customized
Voltage
24VT48VT110V 220V 380V
Current
Customized
Single Voltage Measurement Type
2V/6V/12V
Single Voltage Measurement Range
2V: 0~4V 6V: 0~8V 12V: 0~15V
Single Voltage Resolution
2V/6V: 0.001V 12V: 0.01V
Whole Group Voltage Measurement Range
0~60VT0~285V
Whole Group Voltage Resolution
0.01V
Discharge Current Working Range
2~300A Can Be Set Continuously, More Than 300A Can
Constant Current Discharge Voltage Range
40~56V
Discharge Current Control Accuracy
0.1A
Current Test Accuracy
1%
Working Voltage
AC220V±15% (DC and AC/DC Optional)
Cooling Method
Strong Air Cooling
Communication
RS232 & SD Port
Display
7-Inch Color LCD Display with Touch Screen
Transport Package
Plywood
Specification
440(L)*225(W)*300(H)mm
Trademark
EP Hipot Electric
Origin
China
HS Code
9030899090
Production Capacity
2000/Year

Product Description

General Information:
EPFD Series Battery Discharge Tester is mainly used for the discharge test of the lead-acid battery of the backup power supply in the telecommunications, mobile, China Unicom, and power DC industries. It is a product with three functions of fast battery capacity testing, online monitoring and capacity verification testing.

Product category (How to select model)
Different voltage and current:
 
Voltage 24V 48V 110V 220V 380V 24/48V 110V/220V
Current 50A 50A 30A 30A 30A 80A/150A 20A/40A
100A 100A 60A 60A 50A 150A/300A 30A/60A
150A 150A 100A 100A      
  300A          
  450A          

Different functions:
Model A Model B Model C
  • Smart load
  • Smart load
  • Single cell monitoring (wired, wireless)
  • Smart load
  • Single cell monitoring (wired, wireless)
  • Quick capacity test
The above are standard products. Special voltage and current levels can be customized. Before place order, please specify: voltage, current, functional model and whether single cell monitoring is wired or wireless.

Features:
  • It has the functions of internal resistance test and capacity evaluation for battery packs.
  • It has the function of online monitoring of the performance of multiple indicators of the battery pack: when the battery pack is in the online discharge, equalizing, and floating state, the battery pack and each single cell can be monitored online in real time. The monitoring content includes: battery integration The group voltage, the voltage of each cell, the charging and discharging current of the battery, the monitoring time of the battery, the charging and discharging capacity of the battery, etc.
  • It has the function of quickly and accurately identifying the pros and cons of batteries.
  • It has the function of checking the discharge test of the battery pack according to a variety of discharge rates, and accurately knowing the true capacity of the battery.
  • The online compensation discharge function realizes dynamic compensation during the entire discharge process to ensure the true constant current discharge of the battery pack.
  • Use the equipment to monitor the voltage of each cell in real time during the online discharge process;
  • Test the entire battery pack with voltages of 24V/48V/110V/220V/380V and cell voltages of 2V, 6V and 12V. The user can choose to set the cell voltage type. Single voltage monitoring module, wired and wireless optional.
  • When doing the capacity discharge test, four discharge termination conditions can be set at the same time: 1.The entire set of voltage termination conditions. 2. Single voltage termination conditions. 3. Discharge time termination conditions. 4. Discharge capacity termination conditions. The ongoing testing process can also be manually terminated as needed;
  • 7-inch color touch screen.
  • Simple and convenient operation: all adopt modular interface, good man-machine dialogue function, simple operation, clear flow, each interface and operation steps have simple prompts, which fundamentally avoids wrong operation.
  • The meter can directly perform bar graph and curve analysis and curve comparison functions on the main test results. The voltage curve can be continuously enlarged and reduced for easy observation. Data can be analyzed clearly without uploading to a PC.
  • Discharge parameter template function, directly call preset parameters to discharge test. The intelligent judgment program can intelligently judge whether the monomer falls off. If the monomer falls off, the test will not be interrupted. Input terminal overvoltage protection, LCD prompt, buzzer alarm.
  • Over current protection, LCD prompt, buzzer alarm. Battery voltage polarity reverse protection, LCD prompt, buzzer alarm.
  • Complete communication function, with RS232 communication interface and SD card interface. The data is transferred to the computer for storage management, and long-term historical data storage and analysis can be carried out. Use SD card to transfer data, test and save at any time, light and portable, safe and reliable.
  • The main body of the tester adopts the integrated design of the monitoring part and the power part, and the power part adopts new high-efficiency devices.
  • New special low-heat and high-efficiency load materials and control technology are used to ensure high constant current accuracy.
  • The instrument has a parallel function and can also be connected to an external load, so that the instrument can test various large-capacity batteries.
  • PC software analysis function: provide data management, printing, analysis, report statistics, automatic generation of test reports and reports.
  • The voltage curve can be continuously enlarged and reduced for easy observation. Quickly find historical records.
  • With automatic test protection function: when the whole group or single battery is detected during the test process, the test will be automatically terminated to prevent over-discharge of the battery and completely avoid impact on the equipment. It can also be manually terminated as needed The testing process.
  • After the test is completed, all calculation results are automatically displayed, and maintenance suggestions are provided according to the specific test data.
  • Storage mode: internal storage or external storage can be selected. The minimum interval of internal storage is 1 minute. The minimum external storage is 5 seconds.
24V	48V	110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary BatteryMore details about EPFD Series Battery Tester, please contact EPHipot Electric, we have professional tech team to design correctly designed products and systems.

24V	48V	110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary Battery
24V	48V	110V 220V 380V Battery Discharge Tester/Battery Test /Battery Charger and Discharger for Lead Acid Stationary Battery
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier