Customization: | Available |
---|---|
Mass Scope of Workpiece: | <900kg |
Type: | Universal Testing Machine |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Name | Model | Quantity | Remark |
Cable Fault Tester | EPDL-A | 1 | Rough measurement of main insulation. 12.1-inch industrial control integrated machine, touch operation |
Cable Fault Locator | EPDL-D | 1 | LCD display, sound and magnetic synchronization |
HV Pulse Generator | EPDL-H | 1 | 8kV/64μF, 16kV/16μF, 32kV/4μF three-speed cart type, power 2048J |
Pulse amplitude: | 100Vpp |
Pulse width: | 0.1uS and 2uS |
Measuring distance: | Smax: 60km |
Smin: 15m | |
Measurement error: | absolute error of rough measurement: ±10m |
Relative error of rough measurement: | ±1% |
Temperature resolution | 0.1ºC |
Acousto-magnetic synchronization pin-pointing Cable Fault Locator function: | |
Sound channel: | Maximum signal gain: >=80dB |
Fixed-point accuracy: 0.1m |
|
Magnetic field channel: | Max. signal gain: >80db |
Battery: | Built-in lithium-ion battery pack, nominal voltage 7.4V, capacity 3400mAH |
Use time: | Continuous use time > 7 hours |
Charger: | Input AC220V±10%, 50Hz. Nominal output 8.4V, 1A |
Charging time: | <6 hours |
Display mode: | Transflective 320×240 monochrome liquid crystal |
Volume: | Host 200mm×195mm×120mm |
Weight: | Host 2.0kg |
Sensor 2.5kg | |
Use conditions: | Temperature:-10ºC-40ºC |
Humidity 5-90%RH | |
Altitude <4500m |
Impact high voltage: | 0~8/16/32kV three gears optional |
High voltage divider: | voltage accuracy level 1.5 |
Built-in capacitance: | 4μF/32kV, 16μF/16kV, 64μF/8kV |
Discharge power: | all 2048J |
Impact time: | automatic impact about 4 seconds, manual impact arbitrary control time |
Impact power: | 2KVA |
Volume: | 534L×444W×805H |
Weight: | not more than 75KG |
Power supply: | AC 220V±10% 50Hz±2Hz |
Ambient temperature: | -20~+50ºC |