Portable Automatic Capacitance & Dielectric Loss Tan Delta Test Set for Transformer

Product Details
Customization: Available
Accuracy Grade: 1
Display: LCD
Manufacturer/Factory, Trading Company
Diamond Member Since 2019

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
1000000 RMB
Plant Area
>2000 square meters
  • Portable Automatic Capacitance & Dielectric Loss Tan Delta Test Set for Transformer
Find Similar Products

Basic Info.

Model NO.
EPJS-10/kV/12kV
Power Source
AC220V
Output Voltage
0.5~12kv
Cx Accuracy
+-(Read*1%+1PF)
Tg&Delta Accurancy
+-(Read*1%+0.00040)
Internal Hv
3PF~50000PF/12kv 60PF-1UF/0.5kv
External Hv
3PF~1.5UF/12kv 60PF~30UF/0.5kv
Resolution
Max. 0.001PF, 4 Significant Figures
CVT Self Excitation LV Output
Output Voltage 3~50V, Output Current 3~30A
Test Current Range
10ua~5A
Setting Voltage Range
0.5~12kv
Keywords
C&Df Tester
Test Frequency
45, 50, 55, 60, 65Hz Single Frequency
Test Frequency,Hz
45/55Hz, 55/65Hz, 47.5/52.5Hz Auto Double Frequenc
Frequency Precision
+-0.01Hz
Communiation Port
RS232
Printer
Build-in Thermal Printer
Transport Package
Plywood Case with Foam Inside
Specification
460*360*350mm
Trademark
EP Hipot Electric
Origin
China
HS Code
9031809090
Production Capacity
500/Year

Product Description

General Information: 
EPJS-12kV Capacitance & Disspation Factor Tester is a new generation, fully automatic on-site measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA and etc. 


Features: 
  • High accuracy and wide measurement range
  • Automatic measurement process
  • Measures capacitive, resistive or inductive test objects
  • High accuracy ratio measurements
  • Works with any standard capacitor or resistor value without any recalculations
  • All standard UST and GST configurations

Specifications: 
 
Accuracy:  Cx:  ±(read ×1%+1PF)
Tgδ:  ±(read ×1%+0.00040)
Anti interference:  Frequency conversion anti interference, under 200% interference, still can reach above accuracy. 
Capacitance range:  Internal HV:  3PF~50000PF/12kV 60PF~1μF/0.5kV
External HV:  3PF~1.5μF/12kV 60PF~30μF/0.5kV
Resolution:  Max. 0.001PF, 4 significant figures
Tgδ range:  Unlimited, resolution: 0.001%, capacitance, inductance, resistance can be identified automatically. 
Test current range:  10μA~5A
Inner HV:  Setting voltage range:  0.5~12kV
Max. Output current:  200mA
Increase/decrease voltage:  Continuous slide regulating
Voltage precision:  2%
Voltage resolution:  1V
Test frequency:  45, 50, 55, 60, 65Hz single frequency
45/55Hz, 55/65Hz, 47.5/52.5Hz auto double frequency conversion
Frequency precision:  ±0.01Hz
Outside HV:  UST Positive connection max. Test current 5A, Power frequency or frequency conversion 40-70Hz
GST Negative connection max. Test current: 12kV/5A, power frequency or frequency conversion 40-70Hz
CVT self excitation LV output:  Output voltage 3~50V, output current 3~30A
Measuring duty:  About 36s, it depend on measuring methods
Input power supply:  180V~270VAC, 50Hz/60Hz±1%, local supply or by generator. 
RS232
Build-in thermal printer
Environmental Temperature:  -10ºC~50ºC
Relative humidity:  <90%
Oversize & weight:  460×360×350mm 28kg
Portable Automatic Capacitance &amp; Dielectric Loss Tan Delta Test Set for Transformer

More details on 12kV C&DF Tester please contact EPHipot Electric, we have professional tech team to design correctly designed products and systems. 


Portable Automatic Capacitance &amp; Dielectric Loss Tan Delta Test Set for Transformer
Portable Automatic Capacitance &amp; Dielectric Loss Tan Delta Test Set for Transformer

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier